dc.identifier.citationSANTOS JÚNIOR, Edivaldo Ferreira dos. Impactos do dimensionamento da corrente de magnetização de transformadores na coordenação de funções de proteção de sistemas elétricos. 2021. 62 f. Trabalho de conclusão de curso (Graduação em Engenharia Elétrica) - Unidade Acadêmica do Cabo de Santo Agostinho, Universidade Federal Rural de Pernambuco, 2021.pt_BR
dc.identifier.urihttps://repository.ufrpe.br/handle/123456789/4552-
dc.descriptionOs impactos do dimensionamento da corrente de magnetização de transformadores na coordenação entre funções de proteção contra sobrecorrentes são avaliados neste trabalho. Para tanto, além de testes realizados em sistemas elétricos reportados na literatura, estudos de caso envolvendo dados coletados de um sistema real com geração solar fotovoltaica, situado na região de Petrolina - PE, são analisados. Basicamente, os sistemas ele´tricos foram simulados a partir do software ANAFAS, em que foram calculados os valores das correntes de curto-circuito trifásico, monofásico e monofásico mínimo. Tais valores são utilizados para auxiliar na parametrização das funções de sobrecorrente temporizada e instantânea implementadas no software OCTAVE, assim como no dimensionamento da corrente de magnetização dos transformadores. As saídas das referidas funções de proteção são externadas na forma de coordenogramas, que ilustram as curvas relativas à concessionária e ao cliente (consumidor), além da indicação do ponto relativo à corrente de magnetização. Dos resultados obtidos, constata-se que a corrente de magnetização de transformadores pode impactar na coordenação entre funções de proteção contra sobrecorrentes, afetando os estudos de proteção de empresas que são atendidas por transformadores para suprir sua demanda energética. Nesses casos, inclusive, o dimensionamento incorreto desta corrente pode influenciar na confiabilidade no sistema de proteção das redes de distribuição, ale´m de ocasionar possíveis reprovações destes projetos por parte das concessionárias de energia.pt_BR
dc.description.abstractThe impact of transformers’ inrush currents on overcurrent protection functions is evaluated in this work. To do so, simulation tests are carried out in power systems reported in the literature as well as in real distribution networks located in the region of Petrolina– PE. Basically, the power grids are simulated in the ANAFAS software, in which the three-phase and single line to ground fault currents are computed. These short circuit current values are used as input data in the OCTAVE software to set the instantaneous- and the time-overcurrent protection functions, as well as the transformer’s inrush cur- rent. The overcurrent functions outputs are provided to the user as the utility and consumer time-characteristic curves, indicating also the respective inrush current point in the same plot. From the obtained results, the transformer’ inrush current can directly impact on the overcurrent protection coordination, affecting the protection studies of companies fed by transformer units. In these cases, the incorrect set of such magne- tizing current influence on the protection system reliability, and it may also lead to the protection study disapproval by the utility.pt_BR
dc.format.extent62p.pt_BR
dc.language.isoporpt_BR
dc.rightsopenAccesspt_BR
dc.rightsatribution - non commercial - no derivs 4.0 Brazilpt_BR
dc.rightscreativecommons.org/licenses/by-nc-sa/4.0/deed.pt_BRpt_BR
dc.rightsopenAccesspt_BR
dc.rightsopenAccesspt_BR
dc.subjectcoordenação da proteçãopt_BR
dc.subjectseletividade de produçãopt_BR
dc.subjectcorrente de magnetizaçãopt_BR
dc.subjecttransformadorespt_BR
dc.subjectestudos de proteçãopt_BR
dc.titleImpactos do dimensionamento da corrente de magnetização de transformadores na coordenação de funções de proteção de sistemas elétricospt_BR
dc.typebachelorThesispt_BR
dc.contributor.authorLatteshttp://lattes.cnpq.br/5627386501763054pt_BR
dc.contributor.advisorLatteshttp://lattes.cnpq.br/1139577841043865pt_BR
dc.degree.levelGraduacaopt_BR
dc.publisher.countryBrasilpt_BR
dc.degree.localCabo de Santo Agostinhopt_BR
dc.degree.grantorUniversidade Federal Rural de Pernambucopt_BR
dc.degree.graduationBacharelado em Engenharia Elétricapt_BR
dc.degree.departamentUnidade Acadêmica do Cabo de Santo Agostinhopt_BR
Aparece nas coleções:TCC - Engenharia Elétrica (UACSA)

Arquivos associados a este item:
Arquivo Descrição TamanhoFormato 
tcc_edivaldoferreiradossantosjúnior.pdf2,2 MBAdobe PDFVisualizar/Abrir


Os itens no repositório estão protegidos por copyright, com todos os direitos reservados, salvo quando é indicado o contrário.